Skip to main content
Loading…
This section is included in your selections.

International Building Code Section 2702 is hereby amended to read as follows:

SECTION 2702

EMERGENCY AND LEGALLY REQUIRED STANDBY POWER SYSTEMS

[F] 2702.1 General. Emergency power systems and legally required standby power systems shall comply with Sections 2702.1.1 through 2702.1.8 and Table 2702.

[F] 2702.1.1 Stationary generators. Stationary emergency and legally required standby power generators required by this code shall be listed in accordance with UL 2200.

[F] 2702.1.2 Fuel-line piping protection. Fuel lines supplying a generator set inside a high-rise building shall be separated from areas of the building other than the room the generator is located in by an approved method, or an assembly that has a fire-resistance rating of not less than 2 hours. Where the building is protected throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1, the required fire-resistance rating shall be reduced to 1 hour.

[F] 2702.1.3 Installation. Emergency power systems and legally required standby power systems required by this code or the International Fire Code shall be installed in accordance with the International Fire Code, Washington Cities Electrical Code, NFPA 110 and NFPA 111.

[F] 2702.1.4 Load transfer. Emergency power systems shall automatically provide secondary power within 10 seconds after primary power is lost, unless specified otherwise in this code. Legally required standby power systems shall automatically provide secondary power within 60 seconds after primary power is lost, unless specified otherwise in this code. Transfer to full emergency or legally required standby power shall take place within the maximum time to energize loads specified in Table 2702.

[F] 2702.1.5 Load duration. Emergency power systems and legally required standby power systems shall be designed to provide the required power for a minimum duration of 8 hours for fire pumps serving high-rise buildings in accordance with NFPA 20, and a minimum duration of 2 hours for other systems without being refueled or recharged, unless specified otherwise in this code.

[F] 2702.1.6 Uninterruptable power source. An uninterrupted source of power shall be provided for equipment when required by the manufacturer’s instructions, the listing, this code or applicable referenced standards.

[F] 2702.1.7 Interchangeability. Emergency power systems shall be an acceptable alternative for installations that require legally required standby power systems.

[F] 2702.1.8 Group I-2 occupancies. In Group I-2 occupancies located in flood hazard areas established in Section 1612.3, where new essential electrical systems are installed, and where new essential electrical system generators are installed, the systems and generators shall be located and installed in accordance with ASCE 24. Where connections for hookup of temporary generators are provided, the connections shall be located at or above the elevation required in ASCE 24.

[F] 2702.1.9 Equipment room. If a legally required standby or emergency power system includes a generator set inside or serving a building, the generator set shall be located in a separate room enclosed with 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both, to separate it from the remainder of the building, the transfer switches, and from the normal power source including transformers and distribution equipment. The transfer switches shall also be in a separate room enclosed with 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both, to separate it from the remainder of the building. Power distribution from the emergency source to the emergency transfer switch shall be by an independent route from the normal power source. Independent routes shall mean either a physical separation distance of not less than 50 feet, or a minimum of 1-hour fire-resistance rated separation. System supervision with manual start and transfer features shall be provided at the fire command center or an approved location when a fire command center is not required. Such equipment rooms shall be ventilated directly to the exterior for generator combustion air and radiator cooling air. Any ducts required for such ventilation shall not be dampered and shall be fire-resistance rated to the same level of protection as that required for the equipment room. The requirements of this subsection shall not apply to optional tenant-owned or landlord-owned generator sets.

Exception: Transfer switches shall be permitted to be in the same room as the legally required standby or emergency power system generator sets when inside or serving other than: 1) a high-rise building in accordance with Section 403; 2) an underground building in accordance with Section 405; and 3) a hospital in accordance with Section 407.

[F] 2702.1.10 Smoke control power systems. Smoke control equipment and systems requiring legally required standby or emergency power shall be supplied with two sources of power. Primary power shall be from the normal building power system. Legally required standby power or emergency power shall be from an approved source complying with the Washington Cities Electrical Code. The legally required standby power or emergency power source and its transfer switches shall be in separate rooms from the normal power transformers and switchgears, and ventilated directly to and from the exterior. The room shall be completely enclosed in not less than 1-hour fire barriers constructed in accordance with Section 707, or 1-hour horizontal assemblies constructed in accordance with Section 711, or both, except 2-hour fire-resistance construction shall be required for high-rise and underground buildings per Sections 403 and 405 respectively. Power distribution from the two sources shall be by independent routes to the room containing the automatic transfer switch(s). Independent routes shall mean a physical distance of 50 feet or a minimum 1-hour fire-resistance rated separation. Transfer to full emergency power shall be automatic and shall take place within the maximum time to energize loads. The systems shall comply with the Washington Cities Electrical Code.

EXCEPTION: Ventilation is not required for rooms containing only transfer switches.

[F] 2702.1.11 Fuel-fired generator sets and fuel storage location. Fuel-fired generator sets and associated fuel storage, including optional landlord-owned or tenant-owned generator sets, located more than 75 feet above the lowest level of Fire Department vehicle access, or located at a floor level more than 30 feet below the lowest level of exit discharge, require the approval of the fire code official.

[F] 2702.2 Where required. Emergency and legally required standby power systems shall be provided where required by Sections 2702.2.1 through 2702.2.18 and other sections of this code.

[F] 2702.2.1 Ambulatory care facilities. Essential electrical systems for ambulatory care facilities shall comply with Section 422.6.

[F] 2702.2.2 Elevators and platform lifts. Legally required standby power shall be provided for elevators and platform lifts used as accessible means of egress as required in Sections 1009.4.1 and 1009.5. Emergency power shall be provided for elevators in high-rise buildings where required by Table 2702.

[F] 2702.2.3 Emergency responder radio coverage systems. Legally required standby power shall be provided for emergency responder radio coverage systems required in Section 918 and the International Fire Code. The standby power supply shall be capable of operating the emergency responder radio coverage system for a duration of not less than 12 hours at 100 percent system operation capacity.

[F] 2702.2.4 Emergency voice/alarm communication systems. Emergency power shall be provided for emergency voice/alarm communication systems as required in Section 907.5.2.2.5. The system shall be capable of powering the required load for a duration of not less than 24 hours, as required in NFPA 72.

[F] 2702.2.5 Exhaust systems. Legally required standby power shall be provided for common exhaust systems for domestic kitchens located in multistory structures as required in Section 505.5 of the International Mechanical Code. Legally required standby power shall be provided for common exhaust systems for clothes dryers located in multistory structures as required in Section 504.10 of the International Mechanical Code and Section 614.10 of the International Fuel Gas Code.

[F] 2702.2.6 Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3. The system shall be capable of powering the required load for a duration of not less than 90 minutes.

[F] 2702.2.7 Gas detection system. Emergency or legally required standby power shall be provided for gas detection systems in accordance with the International Fire Code.

[F] 2702.2.8 Group I-2 occupancies. Essential electrical systems for Group I-2 occupancies shall be in accordance with Section 407.11.

[F] 2702.2.9 Group I-3 occupancies. Emergency power shall be provided for power-operated doors and locks in Group I-3 occupancies as required in Section 408.4.2.

[F] 2702.2.10 Hazardous materials. Emergency or legally required standby power shall be provided in occupancies with hazardous materials where required by the International Fire Code.

[F] 2702.2.11 High-rise buildings. Emergency and legally required standby power shall be provided in high-rise buildings as required in Table 2702.

[F] 2702.2.12 Laboratory suites. Legally required standby or emergency power shall be provided for in accordance with Section 5004.7 of the International Fire Code where laboratory suites are located above the sixth story above grade plane or located in a story below grade plane.

[F] 2702.2.13 Means of egress illumination. Emergency power shall be provided for means of egress illumination as required in Section 1008.3. The system shall be capable of powering the required load for a duration of not less than 90 minutes.

[F] 2702.2.14 Membrane structures. Legally required standby power shall be provided for auxiliary inflation systems in permanent membrane structures as required in Section 3102.8.2. Legally required standby power shall be provided for a duration of not less than 4 hours. Auxiliary inflation systems in temporary air-supported and air-inflated membrane structures shall be provided in accordance with Section 3103.10.4 of the International Fire Code.

[F] 2702.2.15 Semiconductor fabrication facilities. Emergency power shall be provided for semiconductor fabrication facilities as required in Section 415.11.10.

[F] 2702.2.16 Smoke control systems. Emergency power shall be provided for smoke control systems as required in Sections 404.7, 909.11, 909.20.6.2 and 909.21.5. Legally required standby power systems shall be provided for pressurization systems in low-rise buildings in accordance with Washington State Building Code Section 504.4.1 and International Building Code Sections 909.20.6 and 909.21.5.

[F] 2702.2.17 Special purpose horizontal sliding, accordion or folding doors. Legally required standby power shall be provided for special purpose horizontal sliding, accordion or folding doors as required in Section 1010.1.4.3. The standby power supply shall have a capacity to operate not fewer than 50 closing cycles of the door.

[F] 2702.2.18 Underground buildings. Emergency and legally required standby power shall be provided in underground buildings as required in Section 405.

[F] 2702.3 Critical circuits. Required critical circuits shall be protected using one of the following methods:

1. Cables, used for survivability of required critical circuits, that are listed in accordance with UL 2196 and have a fire-resistance rating of not less than 1 hour.

2. Electrical circuit protective systems having a fire-resistance rating of not less than 1 hour. Electrical circuit protective systems are installed in accordance with their listing requirements.

3. Construction having a fire-resistance rating of not less than 1 hour.

[F] 2702.4 Maintenance. Emergency and legally required standby power systems shall be maintained and tested in accordance with the International Fire Code.

TABLE 2702

LEGALLY REQUIRED STANDBY AND EMERGENCY POWER

Type of Equipment

Maximum Time to Energize Loads

Minimum Run Time (Duration)

IBC Section

IFC or NFPA Section

Emergency Power Systems1

Exit signs

10 seconds

2 hours

1013.6.3

604.2.9 High rises

604.2.16 Underground buildings

1013.6.3 Exit signs

604.2.13 Temporary tents, canopies, membrane structures

NFPA 70

Exit illumination

10 seconds

2 hours

1008.3

1008.3

604.2.9 High-rises

604.2.16 Underground buildings

Any emergency voice/alarm communication including area of refuge communication systems (barrier-free and horizontal exits)

Per NFPA 72

24 hours (battery); 4 hours (generator)

402.7.3, 402.7.4, and 907.5.2.2 Covered mall buildings

907.2.19 Covered mall buildings

403.4.8 and 907.5.2.2 High-rises

604.2.9 High-rises

405.8, and 907.5.2.2 Underground buildings

604.2.16 Underground buildings

907.2.1, and 907.5.2.2 Assembly occupancies

907.2.1.1 Assembly occupancies

NFPA 72

907.2.11 Special amusement buildings

Fire detection and fire alarm

Per NFPA 72

24 hours (battery); 4 hours (generator)

403.4.8 High-rises

604.2.9 High-rises

405.8 Underground buildings

604.2.16 Underground buildings

909.20.6.2 Smokeproof enclosures

907.6.2 Power supply

907.2.11 Special amusement buildings

907

NFPA 72

Smoke control systems in high-rise buildings, underground buildings and covered mall buildings, and atriums, including energy management systems if used for smoke control

60 seconds

2 hours

403.4.8 High-rises

909.11 Emergency power

404.7 Atriums

405.8 Underground buildings

909.11 Smoke control

Fire pumps in high-rise buildings and underground buildings

10 seconds

8 hours (NFPA 20)

403.4.8 High-rises

604.2.9 High-rises and NFPA 20

405.8 Underground buildings

604.2.16 Underground buildings

913.2 All Fire Pumps

Smokeproof enclosures and elevator shaft pressurization

60 seconds for pressurization

4 hours

403.4.8 High-rises

909 and 909.20.6.2

Any shaft exhaust fans required to run continuously in lieu of dampers in high-rise and underground buildings

60 seconds

4 hours

717.5.3

Fire service or occupant evacuation elevator car operation in high-rise and underground buildings (including control system, motor controller, operation control, signal equipment, machine room cooling/heating, etc.)

60 seconds

4 hours

3003, 3007, and 3008

604.2.9 High-rises

604.2.16 Underground buildings

Elevator car lighting and communications in high-rise and underground buildings

10 seconds

4 hours

3003, 3007, and 3008

604.2.9 High-rises

604.2.16 Underground buildings

604.2.1 Elevators

Lights, heating, and cooling for building fire command center and mechanical equipment rooms serving the fire command center

60 seconds

24 hours

604.2.9 High-rises

Power (other than lights, heating and cooling) for building fire command center

60 seconds

4 hours

Mechanical and electrical systems required by IFC Chapter 27 (hazardous materials including UPS rooms)

60 seconds

4 hours

Chapter 27

Legally Required Standby1

Exhaust fans for any loading dock located interior to a building

60 seconds

4 hours

Transformer vault ventilation equipment

60 seconds

4 hours

Heat tape for sprinkler lines and heating in sprinkler riser rooms

60 seconds

24 hours

Fuel pump system for any legally required system

60 seconds

4 hours

Elevators used for accessible means of egress (in other than high-rise and underground buildings)

60 seconds

2 hours

Elevators (other than fire service or occupant evacuation elevators) in high-rise and underground buildings

60 seconds

2 hours

Any shaft exhaust fans required to run continuously in lieu of dampers (in other than high-rise and underground buildings)

60 seconds

4 hours

717.5.3

Auxiliary inflation systems

60 seconds

2 hours

3102.8.2

3103.10.4

Special purpose horizontal sliding, accordion or folding doors

60 seconds

2 hours

1010.1.4.3

1010.1.4.3

Firefighter air replenishment systems (FARS)

60 seconds

2 hours

919.7.2

919.7.2

FOOTNOTE:

1The fuel pump and associated systems for the emergency or legally required standby generator shall be provided with power from the generator to maintain fuel supply.

(Ord. 6531 § 5, 2020.)