International Building Code Section 3102.8.2 is hereby amended to read as follows:

3102.8.2 Legally required standby power. Wherever an auxiliary inflation system is required, an approved legally required standby power-generating system shall be provided. The system shall be equipped with a suitable means for automatically starting the generator set upon failure of the normal electrical service and for automatic transfer and operation of all of the required electrical functions at full power within the time period indicated in Table 2702 of such service failure. Legally required standby power shall be capable of operating independently for not less than the time period indicated in Table 2702.