23.11.507.5.1 International Fire Code Section 507.5.1 amended – Where required.
This section is included in your selections.
Section 507.5.1 of the International Fire Code is hereby amended to read as follows:
507.5.1 Where required. Where any portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 400 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the Fire code official.
Exception: For Group R-3 and U occupancies equipped throughout with an approved automatic sprinkler system installed in accordance with International Fire Code Section 903.3.1.3, the distance requirement shall be 600 feet.
(Ord. 6532 § 2, 2020.)