Section 604.3 of the International Fire Code is hereby amended as follows:

604.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 m) in depth and 78 inches (1,981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.

Exceptions:

1. Where other dimensions are required or allowed by the electrical code as adopted by the City.

2. Access openings into attics or under-floor areas which provide a minimum clear opening of 22 inches (559 mm) by 30 inches (762 mm).

(Ord. 6532 § 2, 2020.)