23.11.905.3.10 International Fire Code Section 905.3.10 added – Vertical standpipes served by fire pumps in high-rise buildings.
This section is included in your selections.
Section 905.3 of the International Fire Code is hereby amended by the addition of a new subsection 905.3.10 to read as follows:
905.3.10 Vertical Standpipes served by Fire Pumps in high-rise buildings. Where vertical standpipes are served by fire pumps, a check valve shall be installed at the base of vertical standpipe.
(Ord. 6532 § 2, 2020.)