Section 5.4.8 of NFPA Standard 130 is hereby amended to read as follows:

5.4.8 The emergency lighting and communications circuits shall be protected from physical damage by system vehicles or other normal system operations and from fires in the system for a period of not less than 1 hours. The circuits shall be protected from ASTM E 119 fire conditions as required in NFPA 70 (2008) Article 700, Part II 700.9.D(1).