Section 5.5.1 of NFPA Standard 130 is hereby amended to read as follows:

5.5.1* General. The provisions for means of egress for a station shall comply with Section 5.5 and the following International Building Code provisions, except as herein modified;

Maintenance of the means of egress (MOE) system; 1001.2, 1002.1, 1022.1.

Ceiling height; 1003.2, 1011.3.

Protruding objects and encroachment; 1003.3, 1005.7.

Elevation changes; 1003.5.

MOE system continuity; 1003.6, 1005.4, 1006.1.

Posting the maximum occupant load; 1004.9, Posting the maximum occupant load sign is required in enclosed and elevated stations in spaces with a total occupant load of 50 or more as determined by section 5.5.1, item (2).

Outdoor areas; 1004.7, except for at-grade stations.

Multiple occupancies; 1004.4, 1016.2.1, 1006.1.

Egress width and capacity; 1005.2, 1005.3, 1005.5, 1005.6, 1012.2.

Accessible means of egress; 1009.

Doors, gates, turnstiles and door hardware; 1010.

Stairway design; 1011.

Ramp design; 1012.

General signage; 1009.9, 1009.10, 1010.1.9.4, 1010.1.9.8, 1010.1.9.9, 1023.9.

Exit signs; 1013 Exception: Exit signs are not required for at-grade platform stations.

Handrail design; 1003.5, 1005.7.2, 1010.10, 1011.11, 1012.8, 1012.10.2, 1014, 1015.3, 1025.2.3, 1029.6.1, 1029.9.1, 1029.13.1, 1029.16.

Guard rail design; 1015.

Arrangement of exits (exit spread); 1007.1.1.

Boiler, incinerator, furnace, refrigeration machinery and refrigerated rooms; 1006.2 through 1006.2.2.2.

Number of exits or exit access doorways from spaces; 1006.1, except for at-grade open stations.

Corridor design; 1020.

Egress balcony design; 1021.

Exit design; 1022.

Number of exits or exit access doorways from stories; 1006.

Intervening rooms, areas and spaces; 1004.2.1, 1016.2, 1020.6.

Interior stairway and ramps; 1023, 1022.

Exit passageways; 1024.

Exterior exit stairways and ramps; 1027.

Exit discharge; 1028.

(Ord. 6531 § 11, 2020; Ord. 6115 § 1, 2013.)