23.11.1008.3.4 International Fire Code Section 1008.3.4 amended – Duration.
This section is included in your selections.
International Fire Code Section 1008.3.4 is hereby amended to read as follows:
1008.3.4 Duration. The emergency power system shall provide power for a duration of not less than 90 minutes, or such time as stipulated by Section 2702 and Table 2702 when applicable for high-rise or underground buildings, and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with International Building Code Section 2702.
(Ord. 6532 § 2, 2020.)